Commissioning

corridorFUNCTION

 

Activating and deactivating the corridorFUNCTION V2

 

Activating the corridorFUNCTION V2 via mains voltage

Activating the corridorFUNCTION V2 is simple. If an a.c. voltage of 230 V is applied to the digital interface of the LED driver for a period of at least 5 minutes the LED driver detects the corridorFUNCTION V2 and automatically activates it. Activation is required only once per device. There are different procedures for activating by the mains voltage. The requirements are the same in each case.
 

Requirements

  • The LED driver is correctly installed in the luminaire
  • Input voltage is applied
  • A motion sensor is connected to information DA/N or DA/L

Procedure Version 1

  • Remain in the activation range of the motion sensor for more than 5 minutes
    • The motion sensor detects movement and switches on
    • The corridorFUNCTION V2 is activated automatically after 5 minutes
    • The light value switches to presence level (default: 100 %)

Procedure Version 2

  • Set the run-on time on the motion sensor to a value greater than 5 minutes
  • Remain in the activation range of the motion sensor for a short time
    • The motion sensor detects movement and switches on
    • The corridorFUNCTION V2 is activated automatically after 5 minutes
    • The light value switches to presence value (default: 100 %)
  • Reset the run-on time of the motion sensor to the required value

Procedure Version 3: Only possible if the motion sensor offers a manual override option

  • Set the slide switch on the motion sensor to the "Never-Off" function
  • Wait 5 minutes
    • The corridorFUNCTION V2 is activated automatically after 5 minutes
    • The light value switches to presence value (default: 100 %)
  • Reset the slide switch on the motion sensor to the "automatic" function
     

 

Deactivating the corridorFUNCTION V2 via mains voltage

  • Connect mains voltage push button to the terminal marked DA/L
  • Connect neutral conductor to the terminal marked DA/N
  • Press the push button 5 times within 3 seconds

 

Activating and adjusting the corridorFUNCTION V2 via the masterCONFIGURATOR

The corridorFUNCTION V2 can be activated and adjusted via the masterCONFIGURATOR. Further information can be found in the masterCONFIGURATOR manual.
 

Activating and adjusting the corridorFUNCTION V2 via companionSUITE

The corridorFUNCTION V2 can be activated and adjusted via companionSUITE. Further information can be found on this page.